| Model |
GH11-1KVA
|
| Capacity |
1000 VA / 800 W
|
| Input | |
| Minimum Switching Voltage |
160 VAC / 140 VAC / 120 VAC / 110 VAC ± 5% (ambient temperature is less than 35 degrees) (depending on the load ratio 100%-80% / 80%-70% / 70-60% / 60%-0)
|
| Minimum Recovery Voltage | 175 VAC / 155VAC / 135 VAC / 125 VAC ± 5% (ambient temperature is less than 35 degrees) (depending on the load ratio 100%-80% / 80%-70% / 70-60% / 60%-0) |
| Maximum Switching Voltage |
300 VAC± 5%
|
| Maximum Recovery Voltage |
290 VAC± 5%
|
| Frequency Range |
40Hz 2 70 Hz
|
| Phase |
Single-phase grounding
|
| Power specifications |
M 0.99 @ 220-230 VAC (input voltage)
|
| Output | |
| Output Voltage |
200/208/220/230/240 VAC
|
| Mains Voltage Range |
± 1% slick mode
|
| Frequency Range (Synchronization Range) |
47 ~ 53 Hz or 57 ~ 63 Hz
|
| Frequency Range (Battery Mode) |
50 Hz ± 0.25 Hz or 60Hz 士 0.3 Hz
|
| Overload |
The ambient temperature is less than 35 degrees:
105%~110%: UPS will automatically shut down after 10 minutes in battery mode, or switch to bypass mode when the input is normal. 110%-130%: When the UPS is in battery mode, it will automatically shut down after 1 minute, or switch to bypass mode when the input is normal. > 130%: The UPS will automatically shut down after 3 seconds in battery mode, or switch to bypass mode when the input is normal. |
| Current Peak Ratio |
3:1
|
| Harmonic distortion |
W 3% THD (linear load);
W 6% THD (non-linear load) |
| Switching Time | |
| Mains Mode to Battery Mode |
Zero
|
| Frequency Conversion to Bypass |
4ms (under standard conditions)
|
| Waveform (Battery Mode) |
Pure Sine Wave
|
| Efficiency | |
| Mains Mode |
88%
|
| Battery Mode |
83%
|
| Battery | |
| Type and Quantity |
12V / 9Ah *2
|
| Charging Current |
1A
|
| Charging Voltage |
27.3VDC ± 1%
|
| Physical | |
| Dimensions (D x W x H) (mm) |
282 x 145 x 220
|
| Net Weight (Kg) |
9.8
|
| Environmental | |
| Operating Humidity |
20-90 % RH @ 0- 40°C (no condensation
|
| Noise |
Less than 50dBA @ 1m
|
| Management | |
| Intelligent RS-232 or USB (optional) |
Supports Windows® 2000/2003/XP, Sta/2008/7/8, Linux, Unix and MAC
|
| SNMP optional |
Support for power management by SNMP administrator and web browser
|
*The output power will be derated to 80% in frequency conversion mode; when the output voltage is set to 200VAC or 208VAC, the output power will be derated to 80%.
**There will be no further notice if the current product specifications are changed








Reviews