Description
The Eaton 9PX11KiRT is a high-performance, 11 kVA / 10 kW true online double-conversion UPS system designed to deliver continuous, clean, and stable power protection for critical IT loads, networks, and data center environments.
Technical Specifications
| Rating (VA / W) |
11KVA / 10KW
|
| Form Factor |
Rack 6U / Tower
|
| Electrical Characteristics | |
| Technology |
On-line double-conversion with Power Factor Correction (PFC) system
|
| Input Voltage |
200/208/220/230/240 V/250 V 1:1
380/400/415 3:1 |
| Input Voltage Range |
176-276 V without derating (up to 100-276 V with derating) 1:1
305 V-480 V without derating (up to 175 V-480 V with derating) 3:1 |
| Output voltage/THDU |
200/208/220/230/240 V +/– 1%; THDU < 2 %
|
| Input frequency range/THDI |
40-70 Hz, 50/60 Hz auto selection, frequency converter as standard, THDI < 5%
|
| Efficiency |
Up to 95% in Online mode
98% in Hi-Efficiency mode |
| Short circuit current |
150 A
|
| Overload capacity |
Terminal block + 4 IEC C19 (16 A)
|
| Connections | |
| Input |
Terminal block (up to 16 mm²)
|
| Outputs |
Terminal block
|
| Outputs with HotSwap Maintenance Bypass |
≥ 0.99
|
| Batteries | |
| Typical backup times at 50 and 70% load* | |
| 9PX |
13 / 9 min
|
| 9PX + 1 EBM |
32 / 21 min
|
| 9PX + 4 EBM |
100 / 70 min
|
| Battery management |
ABM® and Temperature compensated charging method (user selectable), automatic battery test, deep discharge protection, automatic recognition of external battery units.
|
| Communications | |
| Communication Ports |
1 USB port, 1 RS232 serial port (USB and RS232 ports cannot be used simultaneously), 4 dry contacts (DB9),
1 mini terminal block for remote On/Off and 1 for remote power Off, 1 DB15 for parallel operation. |
| Communication slot |
1 slot for Network-MS card (included in Netpack versions), ModBus-MS or Relay-MS cards.
|
| Operating conditions, standards and approvals | |
| Operating temperature |
0 to 40°C continuous
|
| Noise level |
< 50 dB
|
| Safety |
IEC/EN 62040-1, UL 1778 (1:1 version)
|
| EMC, performance |
IEC/EN 62040 -2, FCC Class A (1:1 version), IEC/EN 62040-3 (Performance)
|
| Approvals |
CE, CB report (TUV), UL (1:1 version, 5 & 6kVA only)
|
| Dimensions D x H x W / Weight | |
| UPS dimensions |
440 (19’’) * 260(3U+3U) * 700 mm
|
| UPS Weight |
86 kg (1:1)
88 kg (3:1) |
| EBM Dimensions |
440 (19’’) * 130(3U) * 680 mm
|
| EBM Weight |
65 kg
|
| Power Module Dimensions |
440 (19’’) * 130 (3U) * 700 mm
|
| Power Module Weight |
21 kg (1:1)
23 kg (3:1) |
| Customer service and support | |
| Warranty |
3 Years (UPS/Battery)
|
* Runtimes are shown at 0.7 power factor. Backup times are approximate and may vary with equipment, configuration, battery age, temperature, etc












Reviews
There are no reviews yet.